| MODEL | EA66200 | EA66300 | EA66400 | EA66500 | EA66600 | |||
| Rated capacity | 200 KVA | 300 KVA | 400 KVA | 500 KVA | 600 KVA | |||
| Numbers of power modules | 4 | 6 | 8 | 10 | 12 | |||
| Rated capacity of power module | 50 KVA | |||||||
| INPUT | ||||||||
| Input wiring | 3Ph + N + PE | |||||||
| Rated voltage | 380 / 400 / 415 Vac | |||||||
| Voltage range | 138 ~ 485 Vac (305 ~ 485 Vac without power downgrading;138 ~ 305 Vac with linear downgrading 40%) | |||||||
| Input frequency | 40 ~ 70 Hz | |||||||
| Power factor | ≥ 0.99 | |||||||
| Current distortion | <3% | |||||||
| BATTERIES | ||||||||
| Battery voltage | ± 240 Vdc (±180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) | |||||||
| Number of battery | 40 pcs 12 V batteries ( supports 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable) | |||||||
| OUTPUT | ||||||||
| Output wiring | 3Ph + N + PE | |||||||
| Rated voltage | 380 / 400 / 415 Vac ±1% | |||||||
| Frequency | Synchronized with utility in mains power mode: 50 Hz / 60 Hz ± 0.25% in battery mode: |
|||||||
| Power factor | 0.9 | |||||||
| Voltage distortion | ≤ 1% with liner load / ≤ 3% with non-linear load | |||||||
| Crest factor | 3:1 | |||||||
| Inverter overload capacity | 105% < load ≤ 110%: transfer to bypass in 60 mins 110% < load ≤ 125%: transfer to bypass in 10 mins 125% < load ≤ 150%: transfer to bypass in 1 min Load > 150%: transfer to bypass in 200 ms |
|||||||
| Bypass overload capacity | Load ≤135% for long term; < 1000% load for 100 ms | |||||||
| SYSTEM | ||||||||
| Efficiency | 96 % | |||||||
| Max. number of parallel | 4 units | |||||||
| Transfer time | 0 ms | |||||||
| Protection | Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. | |||||||
| Communications | RS485, dry contacts, SNMP | |||||||
| Display | 7 inches LCD touch screen | |||||||
| OTHERS | ||||||||
| Operating temperature | 0 ~ 40℃ | |||||||
| Storage temperature | - 40℃ ~ 70℃ | |||||||
| Humidity | 0 ~ 95% (non-condensing) | |||||||
| Altitude | ≤1000m. Above 1000m, derating 1% for each additional 100 m | |||||||
| Protection level | IP20 | |||||||
| Noise level at 1 m | <65 dB | <68 dB | ||||||
| Cabinet dimensions (WxDxH) (mm) | 600 × 850 × 2000 | 1200 × 850 × 2000 | 1400 × 850 × 2000 | |||||
| UPS module dimensions (WxDxH) (mm) | 442 × 620 × 130 | |||||||
| Cabinet weight (kg) | 213 | 426 | 426 | 448 | 568 | |||
| UPS module weight (kg) | 32 | |||||||